0800 088 6248
Electronic leak detector probe held against brazed copper pipe joints

F-gas leak checks and records in Egham

F-gas leak checks for premises in Egham, with records you can show an inspector or insurer.

  • Price confirmed before booking
  • Every system listed and checked
  • Records you can show an inspector

How much do F-gas leak checks cost in Egham?

In Egham, guide prices are about £165–£280 per visit, first system, plus VAT. A typical job (leak checks on 3–6 systems in one visit) is £315–£995 plus VAT. We confirm the price once we know how many systems you have.

An F-gas leak check is a legally required inspection of air conditioning and refrigeration equipment containing fluorinated gases at or above 5 tonnes CO2 equivalent.

Covering Egham and nearby

Businesses in Egham range from independent shops and restaurants to offices, clinics and warehouses. Slough is about 9 km away.

We cover every Egham postcode, including TW20. We also cover Staines, Ashford, Surrey and Windsor, all within easy reach of Egham. Compliance visits in Egham are booked around your opening hours and the paperwork is kept for you afterwards.

What the job covers

  • Refrigerant type, charge and CO2e calculation for each system
  • Direct and indirect checks to the required method
  • Labels and records updated
  • Leak repair quote if a leak is found
  • Follow-up check within one month of any repair

Prices in Egham

These guide prices are adjusted for the South East, where labour and access costs run about 15% above the UK guide.

F-gas leak checks guide prices, Egham
ItemGuide price (ex VAT)Inc VATBasis
Leak check, first system (includes attendance)£165–£280£198–£336per visit
Each additional system, same visit£75–£145£90–£174per system
F-gas asset register set-upUp to £455Up to £546per site
Automatic leak detection system£915–£3,395£1,098–£4,074per system

Ex VAT. Leak checks are often combined with a service visit at no extra attendance charge.

The visit, step by step

  1. Asset check

    We record each system's refrigerant type and charge and calculate its CO2e.

  2. Set the frequency

    Each system gets the legal interval for its CO2e and any automatic leak detection.

  3. Check

    The engineer checks joints, valves, components and operating data for signs of leakage.

  4. Record

    Results are recorded and kept on your F-gas log for at least five years.

Points to plan for in Egham

Certified engineers

Leak checks must be done by an engineer holding the right F-gas certification.

Shared buildings

In multi-let buildings, roof space, risers and plant areas are often controlled by a managing agent. We work to their permits and method-statement requirements.

Repairs

If a leak is found it must be repaired without undue delay and re-checked within one month.

Leased premises

If your Egham premises are leased, the landlord's written consent is usually needed for external units, wall penetrations and roof access. We provide drawings and data sheets for the request.

Typical premises in Egham

Compliance in England: refrigerant work falls under GB F-gas rules, and buildings with more than 12 kW of air conditioning in total need a periodic energy inspection (often called TM44).

FAQs for Egham

How much do F-gas leak checks cost in Egham?

In Egham, guide prices are around £165–£280 per visit, first system, plus VAT; a typical job (leak checks on 3–6 systems in one visit) is £315–£995 plus VAT.

Do you also cover Staines, Ashford, Surrey and Windsor?

Yes. Alongside Egham, we also cover Staines, Ashford, Surrey and Windsor. Each has its own page with local guide prices.

Which postcodes do you cover in Egham?

All of them, including TW20. Give us your postcode when you enquire and we will confirm the visit details.

What is CO2 equivalent?

The refrigerant charge in kilograms multiplied by its global warming potential (GWP), divided by 1,000. It puts every refrigerant on the same scale.

How often are leak checks needed?

At least every 12 months from 5 tonnes CO2e, every 6 months from 50 tonnes, and every 3 months from 500 tonnes. Where automatic leak detection is fitted, each interval doubles to 24, 12 and 6 months.

Talk to us about your premises in Egham

The visit price is agreed before we book. We reply with a guide price or available dates.

CallGet a quote