How much do F-gas leak checks cost in Stroud?

In Stroud, guide prices are about £145–£255 per visit, first system, plus VAT. A typical job (leak checks on 3–6 systems in one visit) is £285–£905 plus VAT. We confirm the price once we know how many systems you have.

An F-gas leak check is a legally required inspection of air conditioning and refrigeration equipment containing fluorinated gases at or above 5 tonnes CO2 equivalent.

Working in Stroud

Stroud supports a mix of high-street retail, professional offices, hospitality and light industry. Gloucester is about 13 km away.

That includes premises in GL5 and GU32 and the surrounding districts. We also work in nearby Gloucester, Cirencester and Cheltenham. Many buildings have a mix of older and newer systems, so we record each one separately and nothing is missed.

What the job covers

  • Refrigerant type, charge and CO2e calculation for each system
  • Leak check by an F-gas certified engineer
  • Direct and indirect checks to the required method
  • Labels and records updated
  • Leak repair quote if a leak is found

F-gas leak checks prices in Stroud

Guide prices for Stroud, set for the South West. Your fixed price comes in writing.

F-gas leak checks guide prices, Stroud
ItemGuide price (ex VAT)Inc VATBasis
Leak check, first system (includes attendance)£145–£255£174–£306per visit
Each additional system, same visit£70–£130£84–£156per system
F-gas asset register set-upUp to £410Up to £492per site
Automatic leak detection system£825–£3,050£990–£3,660per system

Ex VAT. Leak checks are often combined with a service visit at no extra attendance charge.

The visit, step by step

  1. Asset check

    We record each system's refrigerant type and charge and calculate its CO2e.

  2. Set the frequency

    Each system gets the legal interval for its CO2e and any automatic leak detection.

  3. Check

    The engineer checks joints, valves, components and operating data for signs of leakage.

  4. Record

    Results are recorded and kept on your F-gas log for at least five years.

Local points to consider

Operator duty

The legal duty sits with the operator — the person or business with actual control over the equipment.

Working hours

Most Stroud businesses prefer noisy work outside trading hours. Early starts, evenings and weekends can be arranged and are priced up front.

Repairs

If a leak is found it must be repaired without undue delay and re-checked within one month.

Conservation areas

Historic streets and listed buildings in and around Stroud are more likely to need planning permission for outdoor units on visible elevations. We check with the local planning authority before work is booked.

Who we work with in Stroud

Two rules matter for most businesses in England: GB F-gas rules (leak checks from 5 tonnes CO2e) and the periodic energy inspection for more than 12 kW of air conditioning.

Questions about F-gas leak checks in Stroud

How much do F-gas leak checks cost in Stroud?

In Stroud, guide prices are around £145–£255 per visit, first system, plus VAT; a typical job (leak checks on 3–6 systems in one visit) is £285–£905 plus VAT.

Do you also cover Gloucester, Cirencester and Cheltenham?

Yes. Alongside Stroud, we also cover Gloucester, Cirencester and Cheltenham. Each has its own page with local guide prices.

Which postcodes do you cover in Stroud?

All of them, including GL5 and GU32. Give us your postcode when you enquire and we will confirm the visit details.

Who is responsible for F-gas compliance?

The operator of the equipment — normally the business with control over it. Contractors do the checks; the operator must make sure they happen and keep records.

How often are leak checks needed?

At least every 12 months from 5 tonnes CO2e, every 6 months from 50 tonnes, and every 3 months from 500 tonnes. Where automatic leak detection is fitted, each interval doubles to 24, 12 and 6 months.

Talk to us about your premises in Stroud

The visit price is agreed before we book. We reply with a guide price or available dates.