F-gas leak checks and records in Thatcham
F-gas leak checks in Thatcham, with the paperwork handled for you.
- Price confirmed before booking
- Every system listed and checked
- Records you can show an inspector
How much do F-gas leak checks cost in Thatcham?
Expect £165–£280 per visit, first system ex VAT in Thatcham; a typical job — leak checks on 3–6 systems in one visit — usually comes to £315–£995 plus VAT. The price is confirmed before booking.
An F-gas leak check is a legally required inspection of air conditioning and refrigeration equipment containing fluorinated gases at or above 5 tonnes CO2 equivalent.
Thatcham and surrounding areas
In Thatcham, typical premises are high-street shops, offices above them, surgeries, salons and local industrial units. Basingstoke is about 20 km away.
That includes premises in RG18 and the surrounding districts. We also work in nearby Newbury, Basingstoke and Reading. Many buildings have a mix of older and newer systems, so we record each one separately and nothing is missed.
What is included
- Refrigerant type, charge and CO2e calculation for each system
- Direct and indirect checks to the required method
- Labels and records updated
- Leak repair quote if a leak is found
- Follow-up check within one month of any repair
Local guide prices for Thatcham
Guide prices for Thatcham, set for the South East. Your fixed price comes in writing.
| Item | Guide price (ex VAT) | Inc VAT | Basis |
|---|---|---|---|
| Leak check, first system (includes attendance) | £165–£280 | £198–£336 | per visit |
| Each additional system, same visit | £75–£145 | £90–£174 | per system |
| F-gas asset register set-up | Up to £455 | Up to £546 | per site |
| Automatic leak detection system | £915–£3,395 | £1,098–£4,074 | per system |
Ex VAT. Leak checks are often combined with a service visit at no extra attendance charge.
What happens on a visit in Thatcham
Asset check
We record each system's refrigerant type and charge and calculate its CO2e.
Set the frequency
Each system gets the legal interval for its CO2e and any automatic leak detection.
Check
The engineer checks joints, valves, components and operating data for signs of leakage.
Record
Results are recorded and kept on your F-gas log for at least five years.
What to think about in Thatcham
Operator duty
The legal duty sits with the operator — the person or business with actual control over the equipment.
Conservation areas
Historic streets and listed buildings in and around Thatcham are more likely to need planning permission for outdoor units on visible elevations. We check with the local planning authority before work is booked.
Repairs
If a leak is found it must be repaired without undue delay and re-checked within one month.
Roof and height work
Flat roofs, high walls and atriums need the right access equipment and edge protection. We plan towers, MEWPs or scaffold before the job, not on the day.
Types of premises we cover in Thatcham
- Hotels and hospitality: quiet bedroom units, public-area cooling and heat recovery for hotels.
Compliance in England: refrigerant work falls under GB F-gas rules, and buildings with more than 12 kW of air conditioning in total need a periodic energy inspection (often called TM44).
Questions about F-gas leak checks in Thatcham
How much do F-gas leak checks cost in Thatcham?
In Thatcham, guide prices are around £165–£280 per visit, first system, plus VAT; a typical job (leak checks on 3–6 systems in one visit) is £315–£995 plus VAT.
Do you also cover Newbury, Basingstoke and Reading?
Yes. Alongside Thatcham, we also cover Newbury, Basingstoke and Reading. Each has its own page with local guide prices.
Which postcodes do you cover in Thatcham?
All of them, including RG18. Give us your postcode when you enquire and we will confirm the visit details.
How long must records be kept?
For at least five years, covering refrigerant type and quantity, additions and recoveries, leak-check dates and results, and who carried out the work.
How often are leak checks needed?
At least every 12 months from 5 tonnes CO2e, every 6 months from 50 tonnes, and every 3 months from 500 tonnes. Where automatic leak detection is fitted, each interval doubles to 24, 12 and 6 months.
Get a guide price for Thatcham
The visit price is agreed before we book. We reply with a guide price or available dates.