F-gas leak checks and records in Didcot
Stay compliant in Didcot: F-gas leak checks arranged, recorded and followed up.
- Price confirmed before booking
- Every system listed and checked
- Records you can show an inspector
How much do F-gas leak checks cost in Didcot?
In Didcot, guide prices are about £165–£280 per visit, first system, plus VAT. A typical job (leak checks on 3–6 systems in one visit) is £315–£995 plus VAT. We confirm the price once we know how many systems you have.
An F-gas leak check is a legally required inspection of air conditioning and refrigeration equipment containing fluorinated gases at or above 5 tonnes CO2 equivalent.
Covering Didcot and nearby
Businesses in Didcot range from independent shops and restaurants to offices, clinics and warehouses. Oxford is about 16 km away.
Postcode districts we cover in Didcot include OX11. Neighbouring towns we cover include Abingdon, Oxford and Thatcham. We give you the records in a form an inspector, insurer or landlord can read, and remind you when the next check is due.
What we do
- Refrigerant type, charge and CO2e calculation for each system
- Leak check by an F-gas certified engineer
- Direct and indirect checks to the required method
- Labels and records updated
- Follow-up check within one month of any repair
Prices in Didcot
These guide prices are adjusted for the South East, where labour and access costs run about 15% above the UK guide.
| Item | Guide price (ex VAT) | Inc VAT | Basis |
|---|---|---|---|
| Leak check, first system (includes attendance) | £165–£280 | £198–£336 | per visit |
| Each additional system, same visit | £75–£145 | £90–£174 | per system |
| F-gas asset register set-up | Up to £455 | Up to £546 | per site |
| Automatic leak detection system | £915–£3,395 | £1,098–£4,074 | per system |
Ex VAT. Leak checks are often combined with a service visit at no extra attendance charge.
How a visit in Didcot works
Asset check
We record each system's refrigerant type and charge and calculate its CO2e.
Set the frequency
Each system gets the legal interval for its CO2e and any automatic leak detection.
Check
The engineer checks joints, valves, components and operating data for signs of leakage.
Record
Results are recorded and kept on your F-gas log for at least five years.
Points to plan for in Didcot
Certified engineers
Leak checks must be done by an engineer holding the right F-gas certification.
Working hours
Most Didcot businesses prefer noisy work outside trading hours. Early starts, evenings and weekends can be arranged and are priced up front.
Repairs
If a leak is found it must be repaired without undue delay and re-checked within one month.
Access and parking
Town-centre jobs in Didcot often come down to access — loading restrictions, parking for the van and getting equipment onto a roof. We check this at survey and plan deliveries around it.
Typical premises in Didcot
- Hotels and hospitality: quiet bedroom units, public-area cooling and heat recovery for hotels.
In England, systems holding 5 tonnes CO2 equivalent of refrigerant or more fall under GB F-gas rules, with regular leak checks and records; buildings with more than 12 kW of air conditioning in total also need a periodic energy inspection.
Common questions from businesses in Didcot
How much do F-gas leak checks cost in Didcot?
In Didcot, guide prices are around £165–£280 per visit, first system, plus VAT; a typical job (leak checks on 3–6 systems in one visit) is £315–£995 plus VAT.
Do you also cover Abingdon, Oxford and Thatcham?
Yes. Alongside Didcot, we also cover Abingdon, Oxford and Thatcham. Each has its own page with local guide prices.
Which postcodes do you cover in Didcot?
All of them, including OX11. Give us your postcode when you enquire and we will confirm the visit details.
How often are leak checks needed?
At least every 12 months from 5 tonnes CO2e, every 6 months from 50 tonnes, and every 3 months from 500 tonnes. Where automatic leak detection is fitted, each interval doubles to 24, 12 and 6 months.
How long must records be kept?
For at least five years, covering refrigerant type and quantity, additions and recoveries, leak-check dates and results, and who carried out the work.
Need F-gas leak checks in Didcot?
The visit price is agreed before we book. We reply with a guide price or available dates.